How to Size the Sump and Overhead Tank for an Apartment Building
How big should the sump and overhead tank be? A worked example for an apartment building: water demand, storage split, fire reserve and the transfer pump.

Two tanks decide whether the taps run in an apartment building: the underground sump that receives the municipal supply, and the overhead tank on the terrace that feeds the flats by gravity. Make them too small and residents run dry every summer. Make them too big and the water stands, the builder loses space, and the structure carries tonnes it didn't need to.
This article walks through how we size them, with a worked example.
This is a general method. Your authority, water supply department or fire department may set their own figures, and they take priority.
Step 1: How many people?
Water demand is worked out per person, so start with the population. For flats, a common basis is five persons per dwelling unit, whatever the number of bedrooms. Some designers use bedrooms plus one or two, which gives a lower figure for studios and a higher one for 4 BHKs. For shops and offices, use the occupant load per square metre for the use, and add any staff.
Example: a stilt-plus-four building with 24 flats (6 per floor) and four shops at the front.
- Flats: 24 × 5 = 120 persons
- Shops: 4 × 4 staff = 16 persons
Step 2: How much water per person?
The figure most often used for flats with full flushing is 135 litres per person per day, from IS 1172 and the national building standards. Some authorities and larger cities use 150 to 200 litres. For offices and shops, about 45 litres per person per day is typical. Hotels, hospitals and restaurants have their own, much higher figures.
Example:
- Flats: 120 × 135 = 16,200 litres/day
- Shops: 16 × 45 = 720 litres/day
- Total: about 16,900 litres/day
If the building has a separate flushing system using recycled or bore well water, take the flushing share (about 45 litres per person in flats) out of the potable demand and size a separate flushing tank.
Step 3: How much storage?
Storage depends on how reliable the supply is. In much of Goa the municipal supply is intermittent, sometimes only a few hours a day, and drops in the dry months, so storage has to carry the building through the gaps.
A common split is:
- Sump: about one day's demand.
- Overhead tank: about a third to a half of a day's demand.
That gives about one and a half days of total storage. If the supply is very unreliable, or tankers are used in summer, the sump can be made bigger. The overhead tank is kept smaller because it sits on the structure.
Example:
- Sump: 1 × 16,900 → 17,000 litres (domestic)
- Overhead tank: 0.5 × 16,900 → 8,500 litres (domestic)
Step 4: Add the fire reserve, separately
If the building needs a downcomer, wet riser or sprinklers, the fire department will require a dedicated fire water reserve. The volume comes from the fire code table for the building's use and height, not from the domestic demand.
Keep it in a separate compartment, or draw the domestic outlet from a level above the fire reserve so the domestic pumps can never empty it. Shared tanks with no protected reserve are one of the most common fire NOC queries.
For a low-rise building with a downcomer, the reserve is usually held in the terrace tank. For a wet riser building, it is usually an underground fire tank feeding the fire pumps, with a smaller terrace tank.
Step 5: Size the transfer pump
The transfer pump lifts water from the sump to the overhead tank. Size it to fill the overhead tank in about one to two hours.
Flow: 8,500 litres in 1 hour ≈ 142 litres/minute ≈ 2.4 litres/second.
Head: the height from the lowest water level in the sump to the inlet of the overhead tank, plus the friction loss in the rising main and fittings, plus a margin.
- Static lift: sump bottom −2.5 m to tank inlet at about +18 m = 20.5 m
- Friction and fittings: about 4 m for a 50 mm rising main
- Total head: about 25 m
Power: P = ρ × g × Q × H ÷ efficiency = 1000 × 9.81 × 0.0024 × 25 ÷ 0.5 ≈ 1.2 kW, so a 1.5 kW (2 hp) pump. Provide two, one working and one standby, with float or level controls so they stop when the tank is full and can't run dry.
Step 6: Check the pressure on the top floor
Gravity supply from the overhead tank gives little pressure to the top floor: often only 2 to 4 m of head at the shower. That is enough for taps, but not for many mixers, rain showers or instantaneous heaters. Options are to raise the tank on a stand, add a small booster pump for the top floor, or use a hydro-pneumatic system for the whole building.
A few practical points
- Two compartments. Split the sump and the overhead tank into two compartments so one can be cleaned while the other stays in use.
- Overflow and vent. Every tank needs an overflow to a visible point, a vent with mesh, and a lockable access cover.
- Monsoon. Sump covers must stand above the flood level of the site, and the sump walls must keep groundwater out.
- Salt air. On the coast, use corrosion-resistant ladders, covers and fittings.
- Space. Show the pump room size and the tank on the architect's drawings early; it is much harder to find room later.