Fire water tank calculator

Find which fire systems a building needs, the main fire pump and the fire water storage, from its use, height and floor area, to NBCS 2026 Part F.

Your building

Results update as you type.

Result

–

    An estimate for early planning, not a design. Your building, site and authority can change the answer.

    How this calculator works

    It follows SP 7:2026, the National Building Construction Standards (NBCS 2026), Part F:

    • Systems: from Table 7A for residential buildings, 7E for business and 7F for mercantile, by height and the largest floor area, with the notes for basements, EV parking and kitchens
    • Protection level: the same tables give a hose (HL) or combined sprinkler and hose (CL) level
    • Flow: from Table 7K or 7M, the sprinkler density over the design area plus the hose streams
    • Storage: the total flow for the minimum duration in the table, with the longer duration shown where the authority can ask for it
    • Main size: from Table 8 where it lists the case

    It is the same calculation our engineers use in our own design software, simplified to the questions that matter for an early estimate.

    Which code does your fire authority use?

    NBCS 2026 replaces NBC 2016, but not every fire authority has moved to it, and many add their own conditions. Before the design, we check which edition and which local rules the fire department applies. See our guides on fire NOC requirements and what NBCS 2026 changes, or our fire NOC drawings service.

    More free calculators

    Frequently asked questions

    Something else you'd like to know? Ask us.

    How big should the fire water tank be for an apartment building?

    Under NBCS 2026, an apartment building with more than 1,000 m² on its largest floor needs a hose protection level of HL-3: 4 hose streams of 270 L/min, so 1,080 L/min for 30 minutes, about 33,000 litres. Basements, EV parking and greater heights increase it.

    When does a building need sprinklers?

    It depends on the use, height and floor area. Under NBCS 2026, apartments above 60 m, hotels from 24 m, most office buildings, and shops and malls with more than 1,000 m² on a floor need them, and so does any basement or EV parking that has to be sprinklered. The calculator shows what applies.

    Is this enough for a fire NOC?

    No. It's an early estimate. A fire NOC needs drawings and calculations for the actual building, prepared to the rules your fire authority applies.

    Want the real numbers for your building? Send us the drawings.

    We'll reply within one working day with what the building needs and a fixed fee for the design.